OSHA requires a visual inspection of every portable fire extinguisher each month and a maintenance check each year (29 CFR 1910.157(e)). You must record the annual check and keep that record for one year after the last entry or for the life of the shell, whichever is less. Employees expected to use an extinguisher need training at hire and at least once a year after. A free checklist and log are below.
Most fire extinguisher checklists online are a single page of tick boxes with no explanation of where the boxes came from. That works until someone asks you which of those checks OSHA actually requires, how long to keep the paper, or what changes on a construction site. This guide answers those questions, then gives you a two-page log you can print today.
How Often Should Fire Extinguishers Be Inspected?
OSHA sets four separate intervals in 29 CFR 1910.157. They are easy to mix up, because each one is done by a different person and recorded in a different way.
| Interval | What happens | Who usually does it | Source |
|---|---|---|---|
| Monthly | A visual inspection of every portable extinguisher | Any employee you assign | 1910.157(e)(2) |
| Annually | A maintenance check, with the date recorded | A fire equipment service company | 1910.157(e)(3) |
| Every 6 years | Empty and maintain stored-pressure dry chemical units that need a 12-year hydrostatic test | A service company | 1910.157(e)(4) |
| Every 5 or 12 years | A hydrostatic pressure test of the cylinder, by extinguisher type | A trained tester with proper equipment | 1910.157(f), Table L-1 |
The 6-year rule does not apply to dry chemical units with non-refillable disposable containers. And when a unit is recharged or hydrostatically tested, the 6-year clock starts again from that date.
For hydrostatic testing, Table L-1 puts most water, foam, carbon dioxide and stainless steel dry chemical units on a 5-year cycle. Stored-pressure dry chemical units with mild steel, brazed brass or aluminum shells, cartridge-operated dry chemical and dry powder units with mild steel shells, and Halon units run on a 12-year cycle. Check the label on each unit, since that tells your service company which cycle applies.
Free Fire Extinguisher Inspection Checklist (Word and PDF)
The template has two pages. Page 1 is a monthly log for up to 15 extinguishers, with a column for each month and the eight checks printed above it. Page 2 is the annual maintenance record, with columns for the 6-year maintenance date and the next hydrostatic test.
Download the Word template (.docx) · Download the printable PDF
Give every extinguisher a unit number and write it on the unit itself. Then the log, the tag and your service company's invoice all point to the same cylinder, and a missing unit shows up as a blank row.
The Monthly Inspection Checklist
OSHA's monthly rule is one sentence: portable extinguishers "shall be visually inspected monthly." It does not list what to look at. The checks below are the ones in common use, and they line up with the steps in NFPA 10, the fire code standard most local fire marshals and insurers enforce. Each one takes seconds.
- 1. It is where it belongs. The unit is in its assigned spot, on its bracket or in its cabinet.
- 2. Nothing is in the way. No pallets, carts or stored material block the path to it or hide it from view.
- 3. The instructions are readable. The label faces outward and you can read the operating steps.
- 4. The pin and seal are intact. The safety pin is in place and the tamper seal is not broken.
- 5. The gauge reads in the green. On a stored-pressure unit, the needle sits in the operable range, not overcharged or empty.
- 6. There is no damage. No dents, rust, leaks, or a cracked or clogged hose and nozzle.
- 7. It feels full. Lift it. A unit that feels light may have discharged.
- 8. The annual service is current. The maintenance tag or record shows a check within the last 12 months.
If a unit fails any check, take it out of service and put a working extinguisher in its place until it is repaired or recharged. That swap is not optional. Under 1910.157(e)(5), you must provide equivalent protection while a unit is away for maintenance.
The Annual Maintenance Check and Your Records
The annual check is where OSHA's paperwork rule sits. Under 1910.157(e)(3), you must record the annual maintenance date and keep that record for one year after the last entry or for the life of the shell, whichever is less. The record must be available to OSHA on request. Stored-pressure extinguishers do not need an internal examination as part of the annual check.
Most small employers hire a fire equipment service company for this. The technician checks each unit, attaches a dated tag, and gives you an invoice listing what was serviced. Copy those dates onto page 2 of the template so the record survives even if a tag gets torn off.
Hydrostatic tests carry their own record. Under 1910.157(f)(16), the certification must show the test date, the signature of the person who did the test, and the serial number or other identifier of the extinguisher. Keep it until the unit is retested or taken out of service, whichever comes first.
Where Extinguishers Must Be Placed
Inspection only helps if the extinguishers are in the right places to begin with. Under 1910.157(c)(1), you must mount, locate and identify extinguishers so employees can reach them without being put at risk. Under 1910.157(d), the maximum travel distance depends on the class of fire:
| Fire class | What burns | Maximum travel distance to an extinguisher |
|---|---|---|
| Class A | Ordinary combustibles: wood, paper, cardboard, cloth | 75 feet |
| Class B | Flammable liquids and gases | 50 feet from the hazard area |
| Class C | Energized electrical equipment | Follows the Class A or B pattern of the area |
One trap: the inspection and maintenance rules in 1910.157(e) still apply even when you do not intend employees to use the extinguishers. Under 1910.157(a), if you have an emergency action plan and a fire prevention plan and your extinguishers are not meant for employee use, paragraphs (e) and (f) still apply. Only a workplace with no extinguishers at all, a total-evacuation policy, and both written plans is exempt from the whole section, and even then only if no other OSHA standard requires an extinguisher. If you go that route, you will need a written emergency action plan to back it up.
Construction Sites: What 1926.150 Adds
Construction work falls under a different standard, 29 CFR 1926.150, and its placement rules are stricter than the general industry ones. Under 1926.150(c)(1):
- Provide at least one extinguisher rated 2A or higher for each 3,000 square feet of protected building area.
- No point in that area may be more than 100 feet from the nearest extinguisher.
- Put at least one 2A-rated extinguisher on each floor. In multistory buildings, put at least one next to a stairway.
- Where more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are in use, provide an extinguisher rated 10B or higher within 50 feet.
- Protect extinguishers that could freeze.
On inspection, the construction standard is less precise. It says extinguishers "shall be inspected periodically" and maintained according to NFPA No. 10A-1970, an old edition it adopted by reference. Rather than argue about what "periodically" means, run the same monthly check on site and log it. Jobsite units get knocked off brackets, buried behind material and borrowed for the next floor, so a monthly walk catches far more than an office check ever would.
The Training Requirement Most Checklists Leave Out
An extinguisher that passes every check still does nothing if nobody knows how to use it. If you provide extinguishers for employee use, 1910.157(g)(1) and (2) require training on the general principles of extinguisher use and the hazards of fighting an early-stage fire. The training happens when someone is hired and at least once a year after that.
Employees you designate to fight fires as part of an emergency action plan need training on the specific equipment they will use, on first assignment and at least once a year after (1910.157(g)(3) and (4)). Run that training alongside your fire drill requirements, so the drill and the extinguisher refresher reinforce each other.
Keep a signed record of who was trained and when. OSHA's rule does not dictate the format, but a dated attendance sheet is what you will be asked for if an inspector questions whether the annual training happened.
Running the Inspection Digitally
Paper logs work until the clipboard goes missing. Safety Team Technologies includes a ready-made Fire Protection checklist in its hazard assessment library. Its 20 questions cover your fire prevention plan, alarm testing, sprinklers, fire doors, and portable extinguishers: whether you have enough of the right type, whether they are mounted where people can reach them, whether recharges are noted on the tag, and whether employees are instructed in their use.
The inspector picks the jobsite, enters their name and the inspection date, answers each question, and can attach photos of anything that needs fixing. Completed checklists download from the Reports page, so the record is there when someone asks for it. Anything that fails can be logged on the Identified Hazard and Correction Record, with a priority, the person assigned, and a corrective action date.
Frequently Asked Questions
How often should fire extinguishers be inspected?
OSHA requires a visual inspection every month and a maintenance check every year. Some stored-pressure dry chemical units also need to be emptied and maintained every 6 years, and every extinguisher needs a hydrostatic test every 5 or 12 years depending on its type.
Does OSHA require a monthly fire extinguisher inspection tag?
Not in those words. 1910.157(e)(2) requires the monthly visual inspection but does not say how to record it. The record OSHA does require is for the annual maintenance check. Your local fire code or NFPA 10 may require a monthly record as well, so most employers initial a tag or a log anyway.
Who can do the monthly fire extinguisher inspection?
Any employee you assign and show what to look for. The monthly check is visual and takes about a minute per unit. The annual maintenance check and hydrostatic testing are different: hydrostatic tests must be done by trained people with the right equipment, which in practice means a fire equipment service company.
How long do you keep fire extinguisher inspection records?
Keep the annual maintenance record for one year after the last entry or for the life of the shell, whichever is less. Keep the hydrostatic test certification until the unit is retested or taken out of service, whichever comes first.
Do employees need fire extinguisher training every year?
Yes, if you provide extinguishers for employees to use. 1910.157(g) requires training on the general principles of extinguisher use and the hazards of fighting an early-stage fire, when someone is hired and at least once a year after that.
Stop chasing the clipboard every month. Safety Team Technologies gives you the Fire Protection checklist and 20 other ready-made hazard checklists, a hazard correction record, and downloadable reports, alongside weekly crew safety training with a completion record for every worker.
This guide summarizes 29 CFR 1910.157 and 1926.150 as published at the time of review. It is general information, not legal advice. Your local fire code, your insurer, or NFPA 10 may set more detailed inspection steps, so follow the strictest rule that applies to your site. For everything else a small employer is expected to keep on file, see the rest of the written programs OSHA expects.